Germany
HomeAboutProductsSystemsProjectsSupportmyOTT
Water level
Discharge
Precipitation
Water Quality
Data Loggers
Multi-Channel Data Loggers
netDL 500/1000
DuoSens
LogoSens
Operating / Reading Unit
Software solution
Communication
System solutions

Productlinks

 
 
 
 
 
Printversion

OTT LogoSens

Technical data


Power supply +8 ... +15.2 V DC; typ. +12 V

Current consumption (at 12 V)
active, measure
active, not measured
sleep, special inputs active
sleep, clock only


approx. 60 mA
approx. 38 mA
approx. 7.5 mA
approx. 0.7 mA

Protection level, inputs up to 36 V (Protection against external voltage (static))
Display graphics-capable DOT Matrix 122 x 32
Clock
Type
Accuracy
Type of buffer battery
Shelf life of buffer battery

Battery-buffered real time clock
±1 minutes/month (0 °C +50 °C)
CR 2032; 3 V
≥ 5 years (recommend replacement after 5 years)
Interfaces Infrared (IrDA), radiation angle 30 °, 2 x RS 232 C; RS 485; SDI-12
Inputs
Voltage inputs (5 V/10 V)
Ri for GND-referenced voltages
Ri for floating voltages
Precision
Resolution
Measurement period

4 MOhm
> 100 MOhm
< 0.1 % FS
1 mV
350 ms
Current input (0(4) ... 20mA)
Ri
Precision
Resolution
Measurement period

typ. 400 Ohm
typ. 0.1 %; max. < 0.3 % FS
1 µA
350 ms
Pt 100
Precision
Resolution
Measuring range
Measurement period

± 0.1 K (without cable)
0.01 K
–35 °C ... +85 °C
1.2 s
NTC (6k)
Measuring range
Precision
Resolution
Measurement period

–50 ... +100 °C
±0.1 K
0.05 K
600 ms
Conductivity
Measuring range
0 µS ... 250 µS
250 µS... 2030 µS
2030 µS ... 100 mS
Precision values < 10 mS
Precision values> 10 mS
TetraCon 96 Measurement Cell
Cable length

Measurement frequency (28 Hz); Resolution 1µS; Measurement period approx. 2.7 s
Measurement frequency (64 Hz); Resolution 1µS; Measurement period approx. 500 ms
Measurement frequency (494 Hz); Resolution 10 µS dropping to 100 µS; Measurement period approx. 1.3 s
< 0.1 % of measurement ±10 µS
< 1.0 % of measurement ±100 µS
Cell constant 0.609 cm-1 ±1.5 %, NTC < ±0.2 °C Temperature drift < 30 ppm/°C
max. 100 m

Impulse input
Frequency
Debouncing
min. impulse duration
max. contact resistance

0 ... 50 Hz
8.8 ms
8.8 ms
500 Ohm
Frequency input
Frequency
Precision
1 Hz ... 500 Hz
500 Hz ... 6 kHz
Pulse width
Precision
166 µs ... 500 µs
500 µs ... 5 ms
5 ms ...1000 ms
Duty cycle (pos. impulse width/period duration)
Precision
1 Hz ... 10 Hz
10 Hz ... 100 Hz
100 Hz ... 1 kHz
1 kHz ... 3 kHz

1 Hz ... 6 kHz

±0.1 Hz
±1.0 Hz
166 µs ...1000 ms

< 3.0 %
< 0.3 %
< 0.1 %
0 ... 1 (Frequency 1 Hz ... 3 kHz)

Duty cycle 0 ... 1 < ±0.1 %
Duty cycle 0 ... 1 < ±1.0 %
Duty cycle 0,2 ... 1 < ±2.0 %
Duty cycle 0,4 ... 1 < ±2.3 %

SPI input with Thies wind input card
Wind speed [0.1m/s]
Wind direction [0 ... 360 °]
Maximum wind speed [0,1m/s]
Measurement period

vector mean (1 s/60 s)
vector mean (1 s/60 s)

per measurement 1 s
Outputs
Relay outputs
Current resistance
Voltage
Leakage current
bounce-free
max. 1.6 A; electron. short circuit protection with automatic recognition
max. 28 VDC
< 5 µA /28 VD
4 ... 20 mA (galvanically separated)
External power
Precision
Resolution
Load
Ripple (20 mA)
Load dependence
Potential
Insulation
Temperature drift
Power supply drift

max. 42 V
< 0,1 % FS (at 20 °C and 12 V supply voltage)
2 µA
< 350 Ohm (referenced to 8 V minimum supply voltage)
< 100 µA eff.
< 1 ‰
floating (galvanically separated)
> 500 V
< 100 ppm/Kelvin
< 1 ‰/V
Output voltages
+5 V
Vbat
–12 V

1 A
loop power supply
100 mA
Data memory
Storage space available for measurements 917.000 Byte
Storage space needed
per measurement
per channel and day block
info channel, per entry

8 Byte
max. 24 Byte
8 Byte
EMC Limits
Resistance against electrostatic discharge (ESD) complies with EN 61000-4-2 Test level 2 (4 kV contact discharge)
Resistance to electromagnetic fields complies with EN 61000-4-3 Environment class 2 (3 V/m)
Resistance to transient disruptions (burst) complies with EN 61000-4-4 Installation class 5 (4 kV)
Resistance to sudden electrical surges (surge) complies with EN 61000-4-5 Installation class 5 (4 kV)
Interference, electrical/magnetic interference strength complies with EN 55022 Class B (30 ... 1000 MHz)
Mechanical Limits
Dimensions L x W x H 216 mm x 142 mm x 48.5 mm
Weight approx. 0.44 kg
Housing material ABS
Type of protection IP 30
Temperature range –30 °C ... +70 °C




germanenglish HomeNewsSitemapContactSearchImprint & Privacy Policy